Install industrial chiller by yourself? Pay attention to these aspects, you will be rewarded.
Although
Senho Chiller provides installation guidance service, if you already have some
experiences in chiller operation and installation, you can choose to proceed by
yourself to save labor cost and time.
But
first we need to stop thinking that chiller installation is simple enough, that
we just need to connect it to electricity and water, it can just work well by
itself. Pay attention to a few more details, the chiller will return you better
performance and longer service life.
Here are
the precautions that you need to know before proceed:
1.
Selection of installation location.
For air
cooled chillers, we need an open space with good ventilation. Make sure there
is no barriers or walls within 1m around it, otherwise there will be trouble
for air flow and heat dissipation. The point is we need to make sure the heat
out from the chiller can be removed outside, instead of circulating within a
small space. The distance to block also ensures space for maintenance. If you
are planning to install an air cooled chiller in a space with poor ventilation,
you need to consider mounting air duct on top of the chiller near the condenser
fans, so to make sure heat removal.
In below
picture, Case1 is a chiller located in drafty condition, Case 2 is a chiller
located in poor ventilation environment.
For
water cooled chillers, we just need to reserve enough space for maintenance, as
the heat from the chiller is removed through water to the cooling tower.
2.
Ground for locating the chiller.
Industrial chiller must be placed on solid and level concrete floor which is able to
support the weight of the chiller. The levelness of the floor should be within
6mm. Chillers vibrate when running, if the floor is not solid nor flat, the
chiller will easily displace, especially for portable chiller with castors. Rough
ground will amplify the vibration of chiller, which will lead to serious
troubles after long time running.
For a
large chiller unit, say models higher than CRA/CRW60, we need to build concrete
foundation for it. It is necessary to make 50-100mm absorbing gap fill with
sands or pitch all around the foundation. On the foundation, there should be
bolt holes for fastening the chiller base and concrete foundation together.
After
the above things are done, let’s put the chiller on the foundation. Then we
need a level meter to check if there is any incline. If there is, put parallels
between chiller base and concrete foundation to adjust it.
3.
Pipe and wire preparation.
In a
Senho chiller specification sheet, there is connection size and max amps for
the unit. Correctly select the pipe and wire size by referring to it.
4.
Put filter at the inlet of chiller.
If you
are not so confident with the water quality in your factory, filtration is a
necessity to avoid the chiller water circuit from trouble.
For
smaller unit, such as models below PRA/PRW10, you might use cup type filters as
below.
For
bigger units, Y type filter is suggested.
For
water cooled chiller, it is important to put filter at inlet of the condenser,
as in most cases, the water from cooling tower contains foreign matters. You
can always choose a proper filter system according to your own condition.
5.
Correctly pipe according to guidance
provided by Senho.
Make sure you are clear that which port
you should connect to. Although there will be sign of inlet or outlet of every
Senho chiller, double check it please.
It is important to know where you should
put the pumps in a cooling system. Here is a short tip, the pump always suck
water from sources. By sources, we mean devices that hold the most water in a
circuit, for example, an external water tank, water basin of cooling tower,
etc.
If you are not using a self-sucking
pump, make sure the pump is located at a lower level than the water level in container,
otherwise the pump might idle.
Put
valves at each side of every device, including chiller unit, pump, water tank,
which you need to maintain every now and then. You definitely don’t want to
waste the water in the circuit and spoil it everywhere when you have to check
the devices.
Water
pressure gauge is a great option, you could find if your water circuit was
blocked or leaking by monitoring the pressure value.
6.
Anti-vibration.
For
larger cooling project, flexible joints at each side of devices with electric
motors are strongly recommended. Flexible joints will save your water piping
from a lot of troubles, including leakage, noise, etc.
Water
pipes should be built on strong support, which does not rely on chiller or
pump.
7.
Consideration of maintenance.
We
mention maintenance space and valves in previous content. In addition to this,
you might consider to mount some assistant devices such as hanging rail.
Most
importantly, if you are going to do installation by yourself, please reach
Senho for assistance, we will be at your service any time.